PipingNotes

Design-Engineering-Construction-Testing & Commissioning of piping

Browsing:

Category: Notes

Note#14

Painting welded joints not affected hydro-test


Note#13

For chemical anchor bolts M16–> use drill bit 18mm –> hole depth +13mm & M20–> use drill bit 24mm –> hole depth +17.5mm


Note#12

1 inch steel wire = 10 ton load (decrease 25% for safety)


Note#11

Pneumatic test pressure= 1.1 design pressure according to ASME (B31.1& B31.3)


Note#10

Hydro-test test pressure= 1.5 design pressure according to (ASME B31.1 & B31.3)


Note#9

(PQR)procedure qualifications record: suggested procedure of welding which reflected in WPS if accepted


Note#8

To calculate stud bolt size (flange thickness+ 1.5bolt dia.)2 + gasket thickness


Note#7

The gap for socket weld 1.5mm to 3mm


Note#6

Welding equipment require from 33A to 63A


Note#5

The welding for stainless steel piping require purging by inert gas


Note#4

Stainless steel pipe bundle always 6m for any size


Note#3

Raised face flanges require ring gasket or spiral wound


Note#2

Flat face flanges require full face gasket


Note#1

Usually large bore piping for sizes ≥ 2.5″, small bore piping for sizes ≤ 2″